› Flat Chat Strata Forum › Living in strata › EV charging when there is no bylaw in place › Current Page
23/03/2023 at 11:16 pm
#68010
Perhaps all that is needed is a resolution to approve charging at up to 15A from each unit’s individual supply with the addition of a 15A socket or a wall-mounted EVSE outlet limited to 15A in each unit’s parking space with all repair and maintenance the responsibility of the relevant unit owner.
AS3000 rules say that 15A sockets are supposed to be on their own circuits. So in this situation, you should have a switchboard in each parking space, one breaker for the 15A socket and another breaker for everything else.